Skip to content

Recusorb

Recusorb R-51R and R-61R

Nominal capacity is 7.3 kg/h on the R-51R and 10 kg/h on the R-61R, at 20°C / 60% RH. Heat recovery is built in, so the dry air leaves cooler.

Recusorb R-51R and R-61R
  • 7.3–10 kg/h

    At 20°C / 60% RH

  • 1,250–1,450 m³/h

    Dry air flow

  • Heat recovery

    Low dry-air temperature

  • 105–110 kg

    Unit weight

Technical data

Nominal capacity is at 20°C / 60% RH. These are the published table values for this model.

Published figure R-51R R-61R
Nominal capacity (kg/h) 7.3 10
Dry air flow (m³/h) 1250 1450
Dry air static pressure (Pa) 100 100
Wet air flow (m³/h) 430 580
Wet air static pressure (Pa) 300 200
Heater power (kW) 9 13.5
Maximum electric consumption (kW) 10.3 14.8
Supply fuse 3 × 230/400 V 50 Hz (A) 32 / 20 50 / 25
Weight (kg) 105 110

Get a quote

Fill out the form for a quick quote to buy or hire this model. Our friendly team will be in touch with pricing, availability and advice to help you choose the right option for your needs.

Or call 01422 312 562

Monday to Friday, 8.30am to 5.00pm

    Features

    • Washable rotor

    • No desiccant carry-over

    • Stainless steel chassis

    • Built-in heat recovery

    • Low dry air temperature

    • Long lifetime

    Next step

    1. Datasheet

      The published datasheet for this model.

      Download the datasheet
    2. This range

      The Recusorb range this model belongs to.

      Open Recusorb
    3. Help choosing

      If the duty is not settled, ask for help rather than naming a model.

      Get help choosing

    Before you send the quote

    What should the quote include?

    The model is already in the message. Add the temperature, the space, and the humidity or dew point. A phone number helps, and it is optional.

    Can I hire this model?

    Yes. Choose Hire equipment on the form. Choose Purchase equipment if you want to buy it.