Recusorb RLZ-81 to RLZ-104

The large Recusorb RLZ models. Nominal capacity runs from 19 to 70 kg/h at 20°C / 60% RH, with dry air from 2,900 to 10,500 m³/h.

Recusorb RLZ-81 to RLZ-104
  • 19–70 kg/h

    At 20°C / 60% RH

  • 2,900–10,500 m³/h

    Dry air flow

  • Six sizes

    RLZ-81 to RLZ-104

  • Heat recovery

    Built in

Technical data

Nominal capacity is at 20°C / 60% RH. These are the published table values for this model.

Published figure RLZ-81 RLZ-82 RLZ-101 RLZ-102 RLZ-102L RLZ-104
Nominal capacity (kg/h) 19 25 30.5 49.5 57 70
Dry air flow (m³/h) 2900 3500 4600 7000 10000 10500
Dry air static pressure (Pa) 300 300 300 300 300 200
Wet air flow (m³/h) 750 1000 1300 2100 2400 2500
Wet air static pressure (Pa) 200 200 200 200 200 200
Heater power (kW) 24 30 40 63 70 80
Maximum electric consumption (kW) 27.6 34.0 43.6 70.4 79.7 91.5
Supply fuse 3 × 400 V / 50 Hz (A) 50 63 80 125 125 160
Weight (kg) 294 325 380 503 585 600

Get a quote

Fill out the form for a quick quote to buy or hire this model. Our friendly team will be in touch with pricing, availability and advice to help you choose the right option for your needs.

Or call 01422 312 562

Monday to Friday, 8.30am to 5.00pm

    Features

    • EC motor or VSD for process and regeneration fans

    • Washable rotor

    • No desiccant carry-over

    • Built-in heat recovery

    • Low dry air temperature

    • Long lifetime

    Options

    These are listed as options, not as equipment fitted on every unit.

    • Steam or gas regeneration heater

    • Pre and post treatment modules

    • Touchscreen showing airflows and coil outputs

    • Modbus, Profibus or BACnet

    • Insulated inlets

    • Stainless steel chassis

    Next step

    1. Datasheet

      The published datasheet for this model.

      Download the datasheet
    2. This range

      The Recusorb range this model belongs to.

      Open Recusorb
    3. Help choosing

      If the duty is not settled, ask for help rather than naming a model.

      Get help choosing

    Before you send the quote

    What should the quote include?

    The model is already in the message. Add the temperature, the space, and the humidity or dew point. A phone number helps, and it is optional.

    Can I hire this model?