Recusorb
Recusorb RLZ-81 to RLZ-104
The large Recusorb RLZ models. Nominal capacity runs from 19 to 70 kg/h at 20°C / 60% RH, with dry air from 2,900 to 10,500 m³/h.
-
19–70 kg/h
At 20°C / 60% RH
-
2,900–10,500 m³/h
Dry air flow
-
Six sizes
RLZ-81 to RLZ-104
-
Heat recovery
Built in
Technical data
Nominal capacity is at 20°C / 60% RH. These are the published table values for this model.
| Published figure | RLZ-81 | RLZ-82 | RLZ-101 | RLZ-102 | RLZ-102L | RLZ-104 |
|---|---|---|---|---|---|---|
| Nominal capacity (kg/h) | 19 | 25 | 30.5 | 49.5 | 57 | 70 |
| Dry air flow (m³/h) | 2900 | 3500 | 4600 | 7000 | 10000 | 10500 |
| Dry air static pressure (Pa) | 300 | 300 | 300 | 300 | 300 | 200 |
| Wet air flow (m³/h) | 750 | 1000 | 1300 | 2100 | 2400 | 2500 |
| Wet air static pressure (Pa) | 200 | 200 | 200 | 200 | 200 | 200 |
| Heater power (kW) | 24 | 30 | 40 | 63 | 70 | 80 |
| Maximum electric consumption (kW) | 27.6 | 34.0 | 43.6 | 70.4 | 79.7 | 91.5 |
| Supply fuse 3 × 400 V / 50 Hz (A) | 50 | 63 | 80 | 125 | 125 | 160 |
| Weight (kg) | 294 | 325 | 380 | 503 | 585 | 600 |
Get a quote
Fill out the form for a quick quote to buy or hire this model. Our friendly team will be in touch with pricing, availability and advice to help you choose the right option for your needs.
Or call 01422 312 562
Monday to Friday, 8.30am to 5.00pm
Features
-
EC motor or VSD for process and regeneration fans
-
Washable rotor
-
No desiccant carry-over
-
Built-in heat recovery
-
Low dry air temperature
-
Long lifetime
Options
These are listed as options, not as equipment fitted on every unit.
-
Steam or gas regeneration heater
-
Pre and post treatment modules
-
Touchscreen showing airflows and coil outputs
-
Modbus, Profibus or BACnet
-
Insulated inlets
-
Stainless steel chassis
Next step
-
Datasheet
The published datasheet for this model.
Download the datasheet -
This range
The Recusorb range this model belongs to.
Open Recusorb -
Help choosing
If the duty is not settled, ask for help rather than naming a model.
Get help choosing
Before you send the quote
What should the quote include?
The model is already in the message. Add the temperature, the space, and the humidity or dew point. A phone number helps, and it is optional.
Can I hire this model?
Yes. Choose Hire equipment on the form. Choose Purchase equipment if you want to buy it.